Jeddah, Kingdom of Saudi Arabia
Cold room systems

Cold rooms and freezers built from the operating requirement

Temperature-controlled rooms for food production, storage, preparation and dispatch — designed from what you store, how it moves and where the room sits, then verified against manufacturer performance data at Saudi ambient conditions.

All solutions
Illustrative AI-generated cooling installation

Overview

A cold room is only as good as the agreement between its envelope, its product load, its air movement, its controls and its refrigeration capacity. Burooj delivers these as one scope: the insulated room, the doors and air control, the refrigeration equipment, the controls and piping, and the installation and commissioning that bring them into service.

Rooms are specified from the operating requirement — product, holding temperature, entry temperature and pull-down period, door dimensions and traffic, ambient, electrical supply and daily load — not from a catalogue size.

Room types

  • Chillers and cold rooms for raw materials, process holding, chilled storage and preparation.
  • Freezers for frozen storage, with wall, ceiling and door construction suited to low-temperature duty.
  • Blast-freezer envelopes — heavy insulated envelopes, doors and floor-interface coordination for rapid-freezing applications.
  • Cooled corridors and loading areas — multi-room stores with temperature zoning and dispatch interfaces.

System scope and key components

  • Insulated wall, ceiling and partition panels (PIR/PU) with project-specific cladding and joint details.
  • Manual sliding or hinged insulated doors, PVC strip curtains and industrial air curtains where required.
  • Condensing units, evaporators, controls, copper piping, valves and refrigeration accessories.
  • Room controllers, temperature monitoring and alarm functions, with project-specific control panels.
  • Installation of panels, doors, piping, insulation and equipment, with electrical-control coordination.
  • Testing, start-up, parameter setting and handover records.

Industries and applications

Food manufacturing (raw-material rooms, process chillers, frozen stores, loading zones); bakeries and frozen foods (dough and ingredient storage, freezer envelopes, blast freezing); cold-chain logistics (multi-room stores, corridors, loading areas); central kitchens; retail and hospitality back-of-house rooms; industrial facilities with temperature-controlled production or storage.

Engineering and equipment selection

The design basis is established before any performance commitment. The heat-load calculation covers transmission, product pull-down, infiltration and internal loads over the operating hours. Typical practice is a 24-hour average load adjusted to a 21-hour operating window, followed by an engineering margin; the final basis is always project-specific.

Selections are then checked at the actual ambient — typically up to +50 °C for Jeddah projects — and at the actual suction and refrigerant conditions. We do not size refrigeration by horsepower alone: final capacity must be supported by manufacturer performance data at the agreed design point.

Typical construction, confirmed per project in the approved submittal: 150 mm PIR walls and ceiling for freezers, 100 mm for chillers, PIR core at a nominal 40–42 kg/m³, PPGI or project-specific food-grade cladding.

Burooj's supply, installation and commissioning scope

Burooj supplies the panels, doors, equipment, controls and accessories; installs them with its own coordination of suspension, floor interface, penetrations and equipment clearances; and commissions the system with pressure and tightness tests, vacuum and dehydration records, refrigerant charging checks, controller and alarm verification, and a temperature pull-down and room-performance review. Handover includes as-built drawings, commissioning records, controller parameters, manuals and warranties.

What we need to assess your project

  • Room dimensions or the space available, and clear-height requirements.
  • Product, holding temperature, entry temperature and the daily or batch load.
  • Door sizes, expected traffic and open-door hours.
  • Site ambient and whether the room is inside a building or exposed.
  • Floor construction and insulation status.
  • Electrical supply available at the room location.
  • Operating schedule and any redundancy requirement.

FAQs

How is the refrigeration capacity decided?

From a heat-load calculation at your operating conditions, then confirmed with the manufacturer's selection data at the design point — not from a rule of thumb per horsepower.

Are automatic doors included?

Room doors are manual sliding or hinged insulated doors unless automatic operation is specifically priced.

Can the rooms be designed for Jeddah summer conditions?

Yes. Selections are checked at the project ambient, typically up to +50 °C, rather than at nominal catalogue conditions.

What warranty applies?

Typically two years on refrigeration equipment and insulated panels against manufacturing defects and one year on installation workmanship, both from handover. The exact terms are stated in each quotation.

Start with your operating requirement

Send us the room size, product, temperature and daily load and we will come back with a first assessment and the questions we still need answered.

Discuss a cold-room project